00:00 |
If you want to monitor exhaust gas temperatures with an M1, this can be achieved in two ways.
|
00:05 |
A thermocouple amplifier can be wired to a spare analogue voltage input or you can add a MoTeC E triple eight or e eight one six expansion unit.
|
00:15 |
The E triple eight has eight built in thermocouple amplifiers, while the E eight one six provides sixteen analogue voltage inputs which can then be used in conjunction with a thermocouple amplifier.
|
00:27 |
You can then wire your each EGT sensor through the expansion unit and the data will be sent to the M1 via CAN.
|
00:34 |
We can configure this function from the ‘Multi Exhaust Temp’ worksheet in the ‘Engine Systems’ workbook here.
|
00:41 |
We will start by enlarging the ‘Calibrate’ element so we can see what we need to configure.
|
00:46 |
The configuration will vary if you are using a thermocouple amplifier of an expansion device for the EGT inputs so first we will look at configuring the inputs directly as analogue voltage inputs.
|
00:58 |
In this case we can leave the ‘E8XX Mode’ set to disabled as this is only used for an expansion device.
|
01:06 |
Likewise the CAN bus is not used.
|
01:09 |
Now we have some diagnostic settings that the M1 will use to decide if the sensor is faulty.
|
01:14 |
As usual, these need to be set outside the normal operating range of the input so they are only exceeded if the input is actually faulty.
|
01:23 |
This works in conjunction with the ‘Diagnostic Delay’ value and the diagnostic values will need to be exceeded for this long before the sensor is considered to be in fault.
|
01:32 |
The default value will be used as the reading for this particular cylinder if the sensor is deemed to be in fault.
|
01:38 |
We will just move out of order for a second and moving down a little, we can define the voltage resource that this particular EGT sensor is wired to and the voltage reference which will depend on which voltage resource you are using.
|
01:51 |
Now we can move back up and set the calibration for the thermocouple amplifier.
|
01:57 |
If the signal is particularly noisy you can also choose to filter the value if necessary.
|
02:03 |
If you are using an expansion unit, we need to go back to the start and enable the ‘E8XX Mode’ and define which CAN bus it is connected on.
|
02:13 |
In this case the ECU will receive the data via CAN so we need to make sure the ‘Voltage Resource’ is set to ‘Not in Use’.
|
02:21 |
Next we need to define which CAN slot the data will come from and these can be viewed from the drop down menu.
|
02:28 |
The inputs listed with ‘TC’ in the title are dedicated thermocouple inputs available on the E triple eight.
|
02:35 |
If the data is coming from an E triple eight thermocouple input, you can leave the ‘CAN Type’ set to ‘Calibrated’ and you don’t need to worry about the ‘CAN Scale’.
|
02:44 |
If you are using an analogue voltage channel from the expansion unit then you will need to set these to suit the input the M1 is receiving.
|
02:52 |
The process for setting up any additional EGT inputs is just a repeat of this process.
|